Air conditioner tripping breaker
- tomschauer
- Admiral

- Posts: 2323
- Joined: March 28th, 2016, 10:52 pm
- Vessel Info: 1998 Carver 355
Suspicious Fishes !
2022 Kawasaki 310X - Location: upper chesapeake bay
- Has thanked: 326 times
- Been thanked: 602 times
Re: Air conditioner tripping breaker
Rather than swapping wires and guessing about the breaker, consider buying or borrowing a clamp on amp meter. You should have your highest amp reading when the compressor starts. Within about 30 seconds after start the amp reading should drop and stay relatively constant. If it stays constant, and 5% or so below the circuit breaker rating and the breaker trips, the breaker needs replaced. If it spikes about five minutes into the running time and trips the breaker, your system most likely has back up electric heat. If this is the case, you either have a problem with the electric heat, or the system replaced one that didn't have electric heat and the circuit cant handle it. An even quicker check would be to look at the name plate on the unit. it should show a "minimum fuse amps" if the breaker is lower than this minimum, the unit was replaced. If this is the case, you should not just up size the breaker. You need to replace the wire between the unit and the breaker. If you want an Quick fix, disable the electric heat. 

- StDuckie
- Scurvy Dog

- Posts: 20
- Joined: March 16th, 2018, 4:50 am
- Vessel Info: 1991 3607 Aft Cabin Cummins 6BTA
- Location: N Ft Myers, FL
- Has thanked: 29 times
Re: Air conditioner tripping breaker
Hello Carver Mates, I need to replace 30 amp AC breaker. Will any 30 amp marine rated breaker work? 

You do not have the required permissions to view the files attached to this post.
- tomschauer
- Admiral

- Posts: 2323
- Joined: March 28th, 2016, 10:52 pm
- Vessel Info: 1998 Carver 355
Suspicious Fishes !
2022 Kawasaki 310X - Location: upper chesapeake bay
- Has thanked: 326 times
- Been thanked: 602 times
Re: Air conditioner tripping breaker
Your picture is pretty dark, so I cant see what you have. If the breaker matches your mounting in the front and connections in the back then yes, any breaker will work. It is most likely a Carling or Blue Sea Systems breaker.
- km1125
- Admiral

- Posts: 3657
- Joined: February 28th, 2017, 6:04 pm
- Has thanked: 81 times
- Been thanked: 1114 times
Re: Air conditioner tripping breaker
It is a special breaker. It is a double-pole breaker, since it's the main, but it also includes the circuit for the reverse-polarity sensing. Perhaps that is what your problem is? Are you SURE that the power you're feeding it is correctly wired?
Here is some language out of the 3607 manual:
Here is some language out of the 3607 manual:
You do not have the required permissions to view the files attached to this post.
- tomschauer
- Admiral

- Posts: 2323
- Joined: March 28th, 2016, 10:52 pm
- Vessel Info: 1998 Carver 355
Suspicious Fishes !
2022 Kawasaki 310X - Location: upper chesapeake bay
- Has thanked: 326 times
- Been thanked: 602 times
Re: Air conditioner tripping breaker
I didn't think of that. When you said AC I was thinking air-conditioning breaker, my bad. I would look at the breaker. As KM shows above, it may be a double pole. Open the panel, and look at the back. If its twice as wide as other breakers and has both hot and neutral wires it is the breaker mentioned, and should be replaced in kind. If not, any breaker will work.
- km1125
- Admiral

- Posts: 3657
- Joined: February 28th, 2017, 6:04 pm
- Has thanked: 81 times
- Been thanked: 1114 times
Re: Air conditioner tripping breaker
tomschauer wrote:Qr Bbpost I didn't think of that. When you said AC I was thinking air-conditioning breaker, my bad. I would look at the breaker. As KM shows above, it may be a double pole. Open the panel, and look at the back. If its twice as wide as other breakers and has both hot and neutral wires it is the breaker mentioned, and should be replaced in kind. If not, any breaker will work.
Well, you were right it was an air-conditioning breaker, as all the circuits on VAC #2 are for air-conditioning!!
But his issue (I think) is the main, as it's the only 30A breaker. The rest are 15A distribution circuits for each of the three units and one for the water pump.
-
Viper
- CYO Supporter

- Posts: 6266
- Joined: July 10th, 2015, 9:58 pm
- Vessel Info: 1989 Carver 3807 Aft Cabin
- Location: Ontario, Canada
- Has thanked: 475 times
- Been thanked: 1791 times
Re: Air conditioner tripping breaker
As Tom said, you want to get the same configuration. There's a few different types and they don't all mount the same way.
- StDuckie
- Scurvy Dog

- Posts: 20
- Joined: March 16th, 2018, 4:50 am
- Vessel Info: 1991 3607 Aft Cabin Cummins 6BTA
- Location: N Ft Myers, FL
- Has thanked: 29 times
Re: Air conditioner tripping breaker
Any suggestions where to get the "main" breaker, as it is connected to two breakers below? I bought what I thought would work, and it doesn't. 

You do not have the required permissions to view the files attached to this post.
- bud37
- Admiral

- Posts: 5182
- Joined: April 23rd, 2015, 10:22 pm
- Has thanked: 604 times
- Been thanked: 1312 times
Re: Air conditioner tripping breaker
Now , maybe you have already but.....open the panel and on the bad breaker that you want to replace will be some info ( small tape tag ), regarding the name of the breaker etc, and from that you should be able to match it from a local guy or blue seas , they are quite common.......good luck and make sure it is electrically dead before any such work, that includes any inverters.
FWIW.....The above is just my opinion.
-
Viper
- CYO Supporter

- Posts: 6266
- Joined: July 10th, 2015, 9:58 pm
- Vessel Info: 1989 Carver 3807 Aft Cabin
- Location: Ontario, Canada
- Has thanked: 475 times
- Been thanked: 1791 times
Re: Air conditioner tripping breaker
It's probably a Carling breaker, pretty common brand on boats. You need to open it up and get info off the breaker. If it's a Carling, it'll have a part number on it too. Or contact Carver with your hull number and they should be able to help.