Kohler generator help

Post by Mrbigler »

I purchased a 1987 3207 that has a generator issue. It is a Kohler 7.5R27 (106276-A), serial #177842.
The generator starts and runs for 30 seconds then shuts down. If I disconnect the ground lead from the magneto the engine will run 1 minute then shut down.
I am a pretty good mechanic but don’t know anything about troubleshooting generators.

I would truly appreciate help with troubleshooting, or if anyone has a service/troubleshooting manual, or if anyone knows a good Kohler repair person in the Sacramento area.

Thanks in advance:
Mike
User avatar
RobGunn
Deck Hand
Deck Hand
Posts: 63
Joined: September 27th, 2017, 3:08 pm
Vessel Info: 1990 Carver 3607 Aft Cabin
"FINALLY"
Location: St. Joe MI
Been thanked: 23 times

Re: Kohler generator help

Post by RobGunn »

I have a similar issue with my Kohler generator. Iv been told that the control board has a relay that has to sense the need for outgoing power or the unit will shut down. Also there is a oil pressure sensor that will shut the generator down if the pressure is to low. Your issue may be one of these? You wont get ANY support from Kohler, iv tried and tried... Your best bet is to find someone local that knows the unit. Maybe a local marina?
User avatar
ColRon
Admiral
Admiral
Posts: 581
Joined: April 24th, 2017, 6:06 pm
Vessel Info: 1989 Carver Santego 3867
“Escape Plan”
Location: Murray, KY
Has thanked: 77 times
Been thanked: 157 times

Re: Kohler generator help

Post by ColRon »

Mrbigler, let me first welcome you aboard. It could be a misadjusted or faulty speed sensor, oil pressure sensor, or bad temp sensor. You will also need to determine if yours has relay circuitry or is solid state. Solid state has 3 switches and 3 fuses on the generator control panel and the relay circuitry on has one switch and two fuses.

There are about 7 difference things that can cause it to shutdown within the first minute. With the three noted above as the first things to check.

Pm me your email address and I can forward an electronic copy of the service manual for the 7.5R genset. This also goes for anyone else who wants a copy of the Service Manual for the 7.5R. I also have an owners and parts manuals too.
Ron
1989 Carver Santego 3867
“Escape Plan”
Murray, KY

:usa:
User avatar
Mrbigler
Scurvy Dog
Scurvy Dog
Posts: 4
Joined: November 15th, 2019, 10:01 am
Vessel Info: 1987 3207 Aft Cabin with Kohler 7.5R27 generator
Location: Sacramento
Been thanked: 3 times

Re: Kohler generator help

Post by Mrbigler »

An update on my Kohler problem. Thanks to Ron for sending me a digital manual that had a troubleshooting guide. My 7.5R27 is a Relay version (not solid state). There is 1 small board with 3 relays, a multi pin connector and a large capacitor. When I unplugged the connector so I could remove the board for closer examination, I noticed one of the board side pins was broke off in the plug. Then pin happened to be the B+ connection. Fortunately I spent 14 years in the 80’s and 90’s as a component level board technician. I took their board home and manufactured a new pin, soldered it in and solved my issue. Generator now runs great and produces power.
Thanks to those who tried to help, I really appreciate it. Mike :usa:
User avatar
ColRon
Admiral
Admiral
Posts: 581
Joined: April 24th, 2017, 6:06 pm
Vessel Info: 1989 Carver Santego 3867
“Escape Plan”
Location: Murray, KY
Has thanked: 77 times
Been thanked: 157 times

Re: Kohler generator help

Post by ColRon »

:clap: glad to hear you got it repaired! :down:
Ron
1989 Carver Santego 3867
“Escape Plan”
Murray, KY

:usa:
User avatar
RGrew176
Admiral
Admiral
Posts: 6652
Joined: August 17th, 2015, 4:07 am
Vessel Info: 2023 SunTracker Party Barge 22 DLX
Location: Southgate, MI.
Has thanked: 72 times
Been thanked: 470 times

Re: Kohler generator help

Post by RGrew176 »

Just love a happy ending.
Rick Grew

2025 Godfrey Xperience 2286 SFLX

2004 Past Commodore
West River Yacht & Cruising Club
User avatar
Keith S
Scurvy Dog
Scurvy Dog
Posts: 36
Joined: October 4th, 2017, 6:02 pm
Vessel Info: 2005 38 Super Sport
Location: Oceanport, NJ
Been thanked: 21 times

Re: Kohler generator help

Post by Keith S »

I find your issue interesting. Removing the grounding lead from the magneto removes the capability of the controller to shut down the engine. Since that gen has a mechanical fuel pump, in theory it should just keep running. It is one of the ways to troubleshoot that model, unless it has an electric fuel solenoid or someone has added an electric fuel pump. The boards and relays should have no impact on it running.