I know its kind of late to chime in but does water flow from the aft ac cooling water overboard discharge when the forward ac is on? You mentioned that it is a single pump system.
Possibly just an issue in the pump relay control for the aft unit?
98 Model 405 A/C Issue
-
Viper
- CYO Supporter

- Posts: 6266
- Joined: July 10th, 2015, 9:58 pm
- Vessel Info: 1989 Carver 3807 Aft Cabin
- Location: Ontario, Canada
- Has thanked: 475 times
- Been thanked: 1791 times
Re: 98 Model 405 A/C Issue
In a single pump system, when any one of the AC units calls for water, it will flow through all the AC units on board. So if you have 3 AC units and you turn on just one, you'll see 3 overboard discharges if each unit has it's own discharge port.
- g36
- Admiral

- Posts: 2115
- Joined: April 7th, 2014, 6:07 pm
- Vessel Info: 1997 Carver 405
- Location: Soddy Daisy TN.
- Has thanked: 7 times
- Been thanked: 654 times
Re: 98 Model 405 A/C Issue
Fwiw. on my add on 3rd unit in my 405 aft cabin it is a totally separate system including its on water pump. I don't know what would have been the setup from carver with 3 units. I know mine was oem with only 2 hvac units so those do share a common relay box.
1997 Carver 405
Crusader xli
The Black Pearl
Soddy Daisy Tn.
Crusader xli
The Black Pearl
Soddy Daisy Tn.
-
Viper
- CYO Supporter

- Posts: 6266
- Joined: July 10th, 2015, 9:58 pm
- Vessel Info: 1989 Carver 3807 Aft Cabin
- Location: Ontario, Canada
- Has thanked: 475 times
- Been thanked: 1791 times
Re: 98 Model 405 A/C Issue
One pump for three units is the norm. I have seen a second pump used in boats that have an additional air conditioning unit in an enclosed flybridge.
- Midnightsun
- CYO Supporter

- Posts: 2984
- Joined: March 27th, 2016, 2:27 pm
- Vessel Info: The Midnight Sun
2007 41CMY
Volvo D6-370's - Location: Montreal, Canada
- Has thanked: 272 times
- Been thanked: 1193 times
Re: 98 Model 405 A/C Issue
I can confirm the factory setup is a single water circulation pump for all 3 units. Any AC that has a call for cooling or heat, will activate the centralized pump.