ac Freon refill
Hello to all!!!!! I had a problem which was answered to the cause of one of my ac units frosting up. The logical solution was that it was low on Freon, ( thanks Hans). Has anyone done this to their units? I found the the service port which was labeled "suction". Makes sense. If you have done this, what did you use as a product? I'm almost sure it's R12. Thanks in advance.
- tomschauer
- Admiral

- Posts: 2323
- Joined: March 28th, 2016, 10:52 pm
- Vessel Info: 1998 Carver 355
Suspicious Fishes !
2022 Kawasaki 310X - Location: upper chesapeake bay
- Has thanked: 326 times
- Been thanked: 602 times
Re: ac Freon refill
Depending on the years its either r-22 or r-410a.
It should have a label stating the refrigerant type and the charge weight.
It should have a label stating the refrigerant type and the charge weight.
- g36
- Admiral

- Posts: 2115
- Joined: April 7th, 2014, 6:07 pm
- Vessel Info: 1997 Carver 405
- Location: Soddy Daisy TN.
- Has thanked: 7 times
- Been thanked: 654 times
Re: ac Freon refill
You must make sure what refrigerant is in the unit. There should be a label for kind and amount it is using.. If you don't have any guages then your just blindly putting it in, which isn't the best option . It can be done but you can also screw it up and can be dangerous ,Also if your low you have leak., if it is r12 its pretty expensive now if you can find it.
1997 Carver 405
Crusader xli
The Black Pearl
Soddy Daisy Tn.
Crusader xli
The Black Pearl
Soddy Daisy Tn.
- buster53
- Admiral

- Posts: 1170
- Joined: May 12th, 2017, 10:41 am
- Vessel Info: 2001, Carver 356
- Location: Gwynn’s Island, VA
- Has thanked: 10 times
- Been thanked: 285 times
- pepmyster
- Admiral

- Posts: 1035
- Joined: June 5th, 2018, 7:17 am
- Vessel Info: 2004 Carver 360 Sport Sedan
8.1 Volvo Penta
Fresh water boating - Location: Ottawa
- Has thanked: 492 times
- Been thanked: 211 times
Re: ac Freon refill
2004, You could be right about the R22. I read a lot and many have written that it was R22.
- tomschauer
- Admiral

- Posts: 2323
- Joined: March 28th, 2016, 10:52 pm
- Vessel Info: 1998 Carver 355
Suspicious Fishes !
2022 Kawasaki 310X - Location: upper chesapeake bay
- Has thanked: 326 times
- Been thanked: 602 times
Re: ac Freon refill
Its definitely not R-12.
For 2004 it should be 410a, but could still be 22.
22 is quite expensive now. About $35 a pound wholesale.
So if its low, you want to find and repair the leak, not just juice it up.
For 2004 it should be 410a, but could still be 22.
22 is quite expensive now. About $35 a pound wholesale.
So if its low, you want to find and repair the leak, not just juice it up.
- pepmyster
- Admiral

- Posts: 1035
- Joined: June 5th, 2018, 7:17 am
- Vessel Info: 2004 Carver 360 Sport Sedan
8.1 Volvo Penta
Fresh water boating - Location: Ottawa
- Has thanked: 492 times
- Been thanked: 211 times
Re: ac Freon refill
I get that. It must be missing just enough Freon to frost. It working but frosts. After all those years, not surprised it missing a bit.
- tomschauer
- Admiral

- Posts: 2323
- Joined: March 28th, 2016, 10:52 pm
- Vessel Info: 1998 Carver 355
Suspicious Fishes !
2022 Kawasaki 310X - Location: upper chesapeake bay
- Has thanked: 326 times
- Been thanked: 602 times
- pepmyster
- Admiral

- Posts: 1035
- Joined: June 5th, 2018, 7:17 am
- Vessel Info: 2004 Carver 360 Sport Sedan
8.1 Volvo Penta
Fresh water boating - Location: Ottawa
- Has thanked: 492 times
- Been thanked: 211 times
Re: ac Freon refill
I cleaned the condenser, air filter. checked the fins. I put a fan directed at it also, same result.
- km1125
- Admiral

- Posts: 3658
- Joined: February 28th, 2017, 6:04 pm
- Has thanked: 81 times
- Been thanked: 1114 times
Re: ac Freon refill
^^^THIS.
I've had a lot of spirited "discussions" with folks on this topic. If you're passing enough 80F air over something, it CAN'T freeze. Something must be restricting the flow somewhere for the evap to even get close to freezing temperatures.
Low pressures in the system will lower both the condensor and evap temperatures, but if the evap coils have enough flow over them the refridgerant will absorb all the BTUs they need to get the temps over freezing VERY quickly. There may be portions of the evap coils that don't get flow that get cold and establish frost or ice, but that should never grow over the rest of the coil if there is enough return air flow.